TF-TFCP

  • Manual fire signaling
  • Complete CSR management
  • ABS Container V0
  • Degree of protection IP44
  • Mounting in glass-break or rearmable execution
  • EN 54-11: 2001+A1: 2005 - EN 54-17: 2005
  • Description
  • Specifications
  • Contents
  • Downloads
  • TECNOFIRE
  • Addressable pushbutton for FIRE ALARM
  • resettable
  • indoor use
  • maximum occupancy 1 address
  • CSR Functions
  • Line separator with double insulator
  • certification EN 54.11 EN 54-17
Device name TFCP01
Description Addressable alarm button
Type of pushbutton Glass breakage - resettable
Installation Type A - For indoor use only
Communication protocol FIRE-SPEED
Address 2 rotary selectors
Frequency of interrogation 2 levels
Communication WITNESS Signaling that can be excluded
Performance criteria 2
Power From loop
Nominal voltage 24VDC
Operating voltage 18V...30VDC
Standby absorption 500μA @ 24V DC in absence of communication
Absorption in alarm 1,6mA @ 24V DC
Line separator Intelligent isolator (no device loss)
Exercise temperature -15°C...+70°C
Relative humidity 10%...93% (in absence of condensation)
Degree of protection IP44
Container ABS V0
Dimensions (L x W x D) 86 x 86 x53mm
Weight 160g
Standards EN 54-11:2001 + A1:2005 - EN 54-17:2005
Certification number 1293-CPR-0418
Year of CE marking 14
Benefit statement number 007_TFCP01
Certification body EVPU
  • Addressable pushbutton for FIRE ALARM