TF-TFMC1

  • Addressable module 1 conventional zone
  • Power supply for conventional optoisolated sensors
  • 2 connection modes input: Alarm/Sighting
  • 1 signaling status token
  • Surface or DIN mounting (TFDIN accessory)
  • Description
  • Specifications
  • Contents
  • Downloads
  • TECNOFIRE
  • 1 zone input for conventional sensors
  • Power supply required 24Vdc
  • max 32 conventional sensors
  • CSR Function
  • Fire-Speed Protocol
  • Line separator (IN/OUT) with double insulator
  • EN Certificate 54 17-18
Device nameTFMC1
Description Module 1 input for conventional detectors
Communication protocol FIRE-SPEED
Address 2 rotary selectors
Frequency of interrogation 2 levels
Communication WITNESS Signaling that can be excluded
Pre-alarm a detector Programmable
Power From loop
Nominal voltage 24VDC
Operating voltage 18V...30VDC
Standby absorption 450μA @ 24V DC in absence of communication
Absorption in alarm 2,5mA @ 24V DC
Line separator Intelligent isolator (no device loss)
External power supplya Range from 18 to 30V DC
SENS+ power supply output Max. absorption. total 500mA
Line absorption at rest Max. 18mA
Current available sensor line Imáx. 70mA ±5mA
Exercise temperature -15°C...+70°C
Relative humidity 10%...93% (in absence of condensation)
Degree of protection IP40
Container ABS V0
Dimensions (L x W x H) 112 x 78 x 25mm
Weight 165g
Standards EN 54-18: 2005/AC: 2007 - EN 54-17: 2005
Approval certificate 1293-CPR-0492
Year of CE marking 15
Benefit statement number 014_TFMC1
Certification body EVPU
  • Addressable module 1 conventional zone input

alt