Device name | TFM50-HP (TFM50-LP) |
Description | Module 5 entries |
Communication protocol | FIRE-SPEED |
Address | 1 rotary-switch + 1dip-switch - 1 direction for each eada(máx.5) |
Frequency of interrogation | 2 levels |
Communication WITNESS | Signaling that can be excluded |
Performance criteria
| 4 |
Input type | Alarm or malfunction |
Power | From loop |
Nominal voltage | 24VDC |
Operating voltage | Range 18V to 30V DC |
Standby absorption | 500μA @ 24V DC in absence of communication |
Absorption in alarm | <2,3mA @ 24V DC (para cada salida) |
Separador de línea | Aislador inteligente (sin pérdida de dispositivos) |
Salidas para repetidores | 9,4V DC 3mA (protegida) |
Temperatura de ejercicio
| -15°C...+70°C |
Humedad relativa | 10%...93% (en ausencia de condensación) |
Grado de protección
| IP40 |
Contenedor | ABS V0 |
TFM50-HP - Dimensiones (L x A x P) - Peso | 144 x 118 x 71,5mm - 230g |
TFM50-LP - Dimensiones (L x A x P) - Peso | 144 x 118 x 38,5mm - 200g |
Normas | EN 54-18: 2005/AC: 2007 - EN 54-17: 2005 |
Certifi cado de homologación | 1293-CPR-0527 |
Año de marcado
| CE 16 |
Número de la declaración de prestación | 018_TFM50 |
Organismo de certifi cación | EVPU |