TF-TFM10

  • Addressable module 1 input
  • 4 operating criteria:
  • alarm, silence, reset or and none
  • 2 connection modes input: Alarm/Sighting
  • 1 output status signaling lamp
  • Surface fixation
  • Description
  • Specifications
  • Contents
  • Downloads
  • TECNOFIRE
  • Addressable micro-module, consisting of a supervised physical/logical unit
  • 1 entry, uniquely identified in the system, occupies 1 address
  • CSR Function
  • Fire-Speed Protocol
  • Line separator (IN/OUT) with double insulator
  • EN Certificate 54 17-18
Device nameTFM10
DescriptionModule 1 entry
Communication protocolFIRE-SPEED
Address2 rotary selectors
Frequency of interrogation2 levels
Communication WITNESS Signaling that can be excluded
Performance criteria 4
Input typeAlarm or Malfunction
Power From loop
Nominal voltage 24VDC
Operating voltage 18V...30VDC
Standby absorption 450μA @ 24V DC in absence of communication
Absorption in alarm 2,3mA @ 24V DC
Repeater output 9,4V DC 3mA (protected)
Line separator Intelligent isolator (no device loss)
Exercise temperature -15°C...+70°C
Relative humidity 10%...93% (in absence of condensation)
Degree of protection IP40
Container ABS V0
Dimensions (L x W x D) 69,5 (or 49,8) x 49,8 x 17mm
Weight 33g
Standards EN 54-18: 2005/AC: 2007 - EN 54-17: 2005
Certificate of homologation 1293-CPR-0490
Year of CE marking 15
Benefit statement number 011_TFM10
Certification body EVPU
  • Addressable module 1 input

alt