Device name | TFM01 |
Description | Module 1 output |
Communication protocol | FIRE-SPEED |
Address | 2 rotary selectors |
Frequency of interrogation | 2 levels |
Communication WITNESS | Signaling that can be excluded |
Performance criteria
| 2 |
Output type | Contact or controlled line |
Activation delay
| Programmable |
Activation time
| Programmable |
Output activation
| Subject to algebraic formula |
Power | From loop |
Nominal voltage | 24VDC |
Operating voltage | Operating voltage Range from 18 to 30V DC |
Absorption in alarm
| 2,3mA @ 24V DC |
Line separator | Intelligent isolator (no device loss) |
Relay contacts | Max. 30V DC 1A (resistive load) |
Auxiliary power out | Range from 18 to 30V DC (max. 500mA) |
Exercise temperature | -15°C...+70°C |
Relative humidity | 10%...93% (in absence of condensation) |
Degree of protection
| IP40 |
Container
| ABS V0 |
Dimensions (L x W x D) | 112 x 78 x 25mm |
Weight | 165g |
Standards | EN 54-18: 2005/AC: 2007 - EN 54-17: 2005 |
Certification number | 1293-CPR-0421
|
Year of CE marking | 14 |
Certification body
| EVPU |