Device name | TFPS-5
|
Description
| Power supply group 28V DC 5A DC [%VAR%] |
Communication protocol
| FIRE-SPEED |
Address
| 2 rotary selectors |
Frequency of interrogation | 2 levels
|
Communication WITNESS | Signaling that can be excluded
|
No network signaling | May be delayed
|
Power | From loop
|
Nominal voltage | 24VDC
|
Operating voltage | 18V...30VDC
|
Line separator | Intelligent isolator (no device loss)
|
Modular power supply | 28V DC 5A (switching fl yback)
|
Power supply current | 230V AC +10% -15% 50Hz
|
Maximum absorbed current | 700mA AC
|
Assignable batteries | 2 da 12V/17Ah (connected in series)
|
Current for battery charger | Maximum 1,5A
|
Reverse polarity protection | Fuse 5A 250V FAST 5x20 LBC
|
Battery disconnection | Automatic with voltage lower than 18V
|
Flammability class | V-2 or higher
|
Internal resistance | 1.5 Ohm
|
Outputs power supply users | 3 independent (protected by polyswitch)
|
Power supply current outputs | 27,6V DC ±1,5% (t. environment 23º C)
|
Maximum current deliverable outputs | 3 x1,1A a 27,6V DC
|
Ripple maximum load | ≤150mVpp
|
Exercise temperature | -5°C...+40°C
|
Relative humidity | 10%...93% (in absence of condensation)
|
Degree of protection | IP30
|
Container | Metallic
|
Dimensions (L x W x D) | 320 x 365 x 170mm
|
Weight | 7,6Kg
|
Standards | EN 54-4:1997+A1:2002+A2:2006 - EN 54-17: 2005
|
Certification number | 0051-CPR-0432
|
Year of CE marking | 14
|
Benefit statement number | 001_TFPS-5
|
Certification body | IMQ
|