DMT-FP9000-4

  • Conventional central 4 areas with LCD screen
  • 2 Siren output
  • 2 alarm and fault outputs and 2 configurable relay outputs
  • Repeater output
  • Up to 30 detectors per zone
  • End-of-line resistance auto detection
  • Description
  • Specifications
  • Contents
  • Downloads
  • DMTECH
  • Conventional fire alarm panel of 4 zones
  • Certificate EN54-2 and EN54-4
  • 2 independent siren outputs
  • 2 auxiliary alarm and fault outputs
  • 2 configurable relay outputs
  • Individual output for repeaters
  • Capacity for 2 12V batteries
  • 4 access levels ((3 user and 1 manufacturer)
  • LCD display with menu for advanced programming
Primary power supplySwitching source 187-252V AC 50-60 Hz 65W max.
Backup power supply2 batteries 12VDC (up to 5 Ah). Ensures minimum 72 hours duration.
Available languagesEnglish, French, Spanish, Turkish, Romanian and Russian.
Number of zones4 zones, up to 30 detectors by area.
Siren outputs2 siren outputs 24VDC. Independent and monitored open collector outputs
Relay outputs4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max.
End of line resistanceAreas fully monitored by end-of-line resistance (4.7K)
Auxiliary Output Voltage24VDC. Protected by resettable electronic fuse 1.85A
Protection IndexIP30
Temperature-5ºC~+45ºC
Material and colourABS, colour: White
Dimensions310 x 240 x 80 mm
Weight1,3Kg
Recommended cableFire cable with a minimum section of 1.0mm (18AWG).
  • Panels
  • Battery cables
  • Fusible
  • End of line resistors

alt